I-8417/I-8437/I-8817/I-8837

ISaGRAF Embedded Controller


 

Communication

The I-8437 / 8837 provides ethernet solutions. It contains 4 communication ports, COM1:RS232, COM2: 10M ethernet , COM3:RS232/RS485, COM4:RS232.

The I-8417 / 8817 provides RS485 solutions. It contains 4 communication ports, COM1:RS232, COM2: RS485, COM3: RS232 / RS485, COM4:RS232.

These different communication ports can provide different kinds of usage include RS485 networking, controller to controller data-exchange, Modbus / Modbus TCP protocol, remote I/O extension, linking with HMI / MMI, program download / upload , and debugging.

 

Modbus & Modbus TCP/IP

Modbus is a widely used communication protocol. The I-8417 / 8817 supports Modbus RTU protocol on RS232 (COM1) and RS485 (COM2). The I-8437 / 8837 supports Modbus RTU protocol on RS232 (COM1) and Modbus TCP/IP protocol on Ethernet (COM2).

Any HMI (for example, Iconics, Intouch, FIX, Citect, Wizcon, Labview, Lablink, ...), Modbus OPC server, touch monitors (for example, The Touch 506, Touch 509, Touch 510) or other MMI devices can easily talk with the I-8xx7 by Modbus protocol. It is easy to find software and devices with the Modbus protocol on the market. Or, by using VB, VC programming, users can design software with Modbus protocol to talk with the controller.

 

 

Modbus Master

The COM1 and COM2 of I-8417/ 8817/ 8437/ 8837 are Modbus slave ports. PC and HMI are the Modbus master and talk with the Modbus slave port of COM1 or COM2 of the controllers. Moreover, I-8xx7 can also provide Modbus Master protocol on either  COM3 or COM4 of the controllers, in order to talk to devices with Modbus slave protocol, such as PLC, RTU, power meter¡K

 

Multi-client Connection

Each I-8437 / 8837 has an Ethernet port and can take your control system to Internet world. Each I-8437 / 8837 has an IP address and with a fixed Ethernet port No. of 502. Up to 5 PCs can link to one I-8437 / 8837 through Ethernet. Another PC or MMI can link to COM1: RS232 port of the I-8437/ 8837. Therefore, the maximum number of clients that can be linked is 6.

For the I-8417/ 8817, the maximum number of clients that can be linked is 2, one linking to COM1: RS232 and the other linking to COM2: RS485.

 

RS485 Network

One PC or HMI can link to one I-7520 converter to talk to a maximun of 255 I-8417 / 8817 controllers on a RS485 network. The I-8417 / 8817 uses COM2:RS485 as its RS485 network port. Each controller on the same RS485 network should set its unique NET-ID to make networking smooth and error-free. The max. distance can be up to 1200 meters with the terminal resistors.

 

Data Exchange via Fbus or Ebus

Fbus ( RS-485 network )

Each I-8xx7 can use its other RS-485 port ( COM3 ) to talk to each other via the Fbus communication mechanism . Fbus can be used to broadcast data to each controller or each controller can request to send or receive data from any other controller on the same Fbus network.

 

Ebus ( Ethernet network)

Each 8437 / 8837 can use its ethernet port ( COM2 ) to talk to each other via the Ebus communication mechanism. When the PC is talking with controllers via ethernet, the controllers can also talk to eachother via the same Ethernet, It makes the configuration more flexible and faster.

 

Sending Email

The ISaGRAF driver inside the I-8417 / 8817 / 8437 / 8837 provides ¡§Email¡¨ function block to send email form the COM4 of the controller via a general modem. Then it will be an useful and easy way to send an alarm message to the system operator. Or it can becom a production report system.

Various IO boards / Remote IO Extension

The I-8417 / 8437 provides 4 empty slots while the I-8817 / 8837 provides 8 empty slots on-board. The IO boards include Digital I/O, Relay output, SSR-DC/AC output, AC input, Strain Gauge input, Analog I/O, RTD, Thermocouple, counter,  frequency, and more. There are more than 30 different I/O boards available now and, in the future, there will be more. The max.  channel provided by the I-8040 / 8041 / 8042 Digital I/O boards is 32.

Remote IO modules are useful for some distributed applications. The I-8417 / 8817 / 8437 / 8837 can integrate with the I-7000 and I-87xx modules by linking one of its COM3 or COM4 ports to each remote I/O module. A max. number of 64 remote I/O  modules can be linked to one controller and max. number of 16 I/O channels for some remote I/O modules.

 

Remotely Download Program: Modem_Link

The Mode_Link is an software designed by ICP DAS, which need to be installed into the ISaGRAF software in your PC. The Modem_Link provide you a easy way to remotely download your ISaGRAF program to the I-8417/ 8817/ 8437/ 8837 via a general modem. And also you can monitor every I/O, data and if the program allows, you can controll it via the Modem.

 

Features & Specifications

  • General environment

    Operating temperature: -25¢XC to +75¢XC

    Storage temperature: -40¢XC to +85¢XC

    Humidity: 0 to 95 % (non-condensed)

    Built-in Watch Dog Timer

    Built-in power protection & network 

    protection circuit

  • System

    CPU: 80188-40 or compatiable

    SRAM: 512K bytes

    FLASH ROM: 512K bytes

    COM4 support full modem signals.

    COM ports for the I-8417 & 8817:

    COM1:RS-232, COM2:RS-485,  

    COM3:RS232/RS485, COM4:RS232

    COM ports for the I-8437 & 8837:

    Ethernet: 10 BaseT

    COM1:RS-232,

    COM3:RS232/RS485, COM4=RS232

    Program download from PC to COM1, COM2 & Ethernet

    Built-in 64-bits hardware unique serial   number

    4 empty I/O slots for I-8417 & 8437 for

    I-8000 parallel & serial I/O boards.

    8 empty I/O slots for I-8817 & 8837 for

    I-8000 parallel & serial I/O boards

    SMMI: Built-in five 7-Seg. Leds, four

    pushbuttons, & three Leds on the front

    panel for using as Simple Man

    Machine Interface.

  • Software

    Supports IEC61131-3: ISaGRAF 

    Programming languages: LD, FBD, SFC, ST, IL & FC

    Real Time Clock

    Year-2000 compliance

    Gives seconds, minutes, hours, date of the month, month and year, from 1980 to 2079

  • NVSRAM

    31 bytes, battery backup, data valid up to 10 years

  • EEPROM

    2048 bytes (8 blocks, each 256 bytes)

    Data retention > 100 years.  1,000,000 erase/write cycles

    l  Flash Memory

    512K bytes, Erase unit is one sector (64K bytes)

    100,000 erase/write cycles

  • COM1

    RS-232: TXD,RXD,RTS,CTS,GND

    Communication speed: 115200 max.

    Supports Modbus Serial Protocol for Connecting PC/HMI & Touch panels

  • COM2 for I-8417 & 8817

    RS-485: Data+, Data-, self-tuner ASIC inside

    Communication speed: 115200 max.

    Supports Modbus Serial Protocol for Connecting PC/HMI & Touch panels

  • Ethernet for I-8437 & 8837

    10 BaseT Connector, 10M bps, NE2000 compatible

    Supports Modbus TCP/IP Protocol for Connecting PC/HMI & Touch panels

  • COM3

    RS232/RS485: 115200 bps max.

    RS232: TXD,RXD,RTS,CTS,GND

    RS485: Data+, Data-

    Supports Protocol of I-7000 & I-87K Remote I/O Modules

    Supports Modbus Master Protocol for connecting other Modbus devices

    Supports User self defined Protocol

  • COM4

    RS232: 115200 bps max.

    Full modem signals: TXD, RXD, RTS, CTS, DSR, DTR, DCD, RI, GND

    Supports Protocol of I-7000 & I-87K Remote I/O Modules

    Supports Modbus Master Protocol for connecting other Modbus devices

    Supports User self defined Protocol

  • Modem_Link

    Supports PC Remotely download the program to faraway controllers through a general Modem. 

  • Controller to Controller Data Exchange

    Supports ¡§Ebus¡¨ software mechanism built in the ethernet port of the I-8437 & 8837 to exchange data with each other.

    Supports ¡§Fbus¡¨ software mechanism built in the COM3:RS485 port  of the I-8417, 8817, 8437 & 8837 to exchange data with each other.

  • Sending Emails

    COM4 supports the software protocol to

    send eamils via one general modem.

  • Power

    Power requirements: 10 to 30V DC (unregulated)

    Power consumption: 20W

Options:

  • DIN-540A: 24VDC, 1.7 Amps. DIN-Rail Mounting Power supply

  • I-workbench-80: ISaGRAF workbench, supports 80 I/O tags

  • I-workbench-256: ISaGRAF workbench, supports 256 I/O tags

  • S-256: 256 KBytes Battery Backup RAM

  • S-512: 512 KBytes Battery Backup RAM

Ordering Information

I-8417

ISaGRAF Controller with 4 empty slots 

I-8817

ISaGRAF Controller with 8 empty slots

I-8437

ISaGRAF Ethernet Controller with 4 empty slots 

I-8837

ISaGRAF Ethernet Controller with 8 empty slots